In short
- F18 is the AC overcurrent fault of the Sunsynk fault table: the AC side of the inverter saw a current peak above its hardware limit.
- Most of the time a load triggers it, a motor starting or too many appliances at once, and more often during a power cut than on grid.
- An F18 that comes back with every load switched off is a matter for your installer.
The fault table of the Sunsynk hybrid manuals lists F18 as an AC overcurrent fault detected by the hardware. The advice printed next to it is short: check that the loads are within the range of the inverter, then restart. The protection is fast on purpose, because it guards the power stage.
Where the current peak comes from
| Cause | How it looks |
|---|---|
| A motor starting | F18 at the moment a borehole pump, a compressor, an air conditioner or a power tool starts. For a second or so, a motor can draw several times its rated current. |
| Too much load at once | Oven, kettle and geyser or immersion heater together on the essential output, with no grid to help. |
| A fault on a circuit | F18 returns as soon as one particular circuit is switched on. A damaged cable or a failing appliance is drawing a short-circuit current. |
| A disturbance from the grid or a generator | F18 with a modest load, during a storm, when the grid comes back after a cut, or while a generator is running. |
| The inverter or its AC wiring | F18 at restart with every load disconnected. |
On grid or on battery: why it matters
While the grid is present, it supplies a good part of a start-up peak. In a power cut or during load shedding, the essential output is fed by the inverter alone. A pump that started for years without a word can then be one peak too many. This is why many owners only meet F18 during cuts, and why the first question is always the same: was the grid there when it happened? Our guide to Sunsynk in a power cut explains which circuits sit on the essential output.
What to check, in order
- What started. Think back to the second before the stop. A code that follows the same appliance has found its cause.
- The total load against the rated power of your model, which is on the side label and in its manual. Add up what runs at the same time, not the average of the day.
- A restart with the loads off. Switch the load breakers off, restart the inverter as your manual describes, then bring the circuits back one by one. The circuit that trips it is the one to have inspected.
- The supply. If the lights flickered at the neighbours too, or the grid had just returned, the disturbance came from outside.
If F18 comes back with nothing connected, stop there and call your installer. That points to the inverter or its wiring, and it is not a job for the owner.
Reading the minute before
Sunsynk Monitor reads the inverter every few seconds: house load, power on the essential output, grid, battery and the current fault code. It keeps these values on the box and, if you turn it on, in the free Cloud, so you can scroll back to the time of the F18. A spike just before the stop names a starting appliance. A high plateau says the house was asking for too much. A flat, low curve sends you toward the supply or the inverter. A very short peak can fall between two readings, so the curve is a strong clue, not a proof.
Keeping it from coming back
- Start large appliances one at a time, above all during a cut. In Home Assistant, an automation can hold the water heater while the oven runs.
- Ask about a soft starter for a pump or a compressor that trips the inverter at each start.
- Ask your installer which heavy loads belong on the essential output. Moving one to the non-essential side lets the grid absorb its start.
- Have a suspect circuit tested before you use it again.
The other frequent codes are in our list of Sunsynk fault codes.
Common questions
How do I reset F18 on a Sunsynk inverter?
Remove the cause first, then restart the inverter as the manual of your model describes. Restarting again and again on the same load only repeats the fault.
Why do I only get F18 during load shedding or a power cut?
On grid, the grid helps with current peaks. On battery, the inverter supplies the essential output alone, so a motor start it never noticed before can exceed its limit.
Is F18 dangerous?
The code is a protection doing its job. The cause can matter: a circuit that trips the inverter every time may hide a damaged cable or appliance and should be tested.
Does Sunsynk Monitor clear the fault or change a setting?
No. Sunsynk Monitor is an independent accessory and it only reads the inverter. It shows the code and the values around it; it never writes a setting.